HTF-III (HTF-W) series
Roof mounted fire smoke exhaust axial flow fan
Product features
Purpose: Fire and smoke exhaust on the roofs of factories and workshops.
Impeller diameter: 400~1400mm
Airflow range: 4500~76000m ³/h
Pressure range: 80~320Pa
Working temperature: 280 ° C/50H
Drive mode: direct motor drive
Humidity:<90%
Medium conditions: Air (with a dust content not exceeding 100mmg/m ³)
Explosion proof type (non corrosive, containing flammable and explosive gases, with a dust content not exceeding 100mg/m ³)
Working power supply: three-phase, 380V/50HZ
Main Features
Adopting a thin plate axial flow impeller, it has the characteristics of high air volume and high efficiency.
The fire protection of the fan has passed the testing of GA211-2009 "High Temperature Resistance Test Method for Fire Exhaust Fans".
The fan casing can be made of materials such as carbon steel spray coating or stainless steel.
The fan impeller can be made of materials such as carbon steel or stainless steel.
The carbon steel fan is treated with sandblasting and coated with double-layer epoxy paint on the surface.
The blade angle can be selected according to different parameters.
The fan is equipped with safety nets and bird proof nets as standard, and optional accessories such as check valves and electric inlet valves can also be provided.